USER’S MANUAL
1000 & 1400 Specifications
200, 220, 230 and 240 V
26
Specification
Pro 1000
Pro 1400
Capacity rating
1000 VA
1400 VA
Nominal input volt.
200, 220, 230, 240 user adjustable
Nominal input freq.
50, 60 Hz auto sensing, user adjustable default
Acceptable input volt.
0 J 33% over the nominal input voltage
On line input freq. limits
+/J 5% over the nominal input freq
Output voltage
+/J 15% from the nominal input volt
Output frequency
+/J 1 Hz from the nominal input freq
Output wave form
PWM. stepped wave approximation to sine wave.
Continuous output capacity
1000 VA, 3J5 min. per batt. set
1400 VA. 3J5 min. per batt. set
Typical back up time
45 min. per batt. set
60 min. per batt. set
Transfer time
2 ms typical, 4 ms max.
Maximum load
1000 VA/670 W
1400 VA/950 W
Noise filter
Full time EMI/R.FI filtering, 100 kHz to 10 MHz
Surge energy rating
480 J
Surge current capability
6500 A
Surge response time
0 ns normal mode, <5 ns common mode
Surge voltage let through
0.7% subject to IEEE 587 Cat. A 6 kV test
Processor
RISC based micro processor
Detection
power source RMS value, locked phase, no load power saving, output load,
opeating temperature, bad battery, battery condition & system fault
Protection
overcurrent, shortJcircuit, overload, lightening, surge, noise, sags, brownout,
blackout, input breaker, modem & 10BaseJT
Battery type
sealed and leak proof maintenance free leadJacid
Alarm signals
Audible signals,
45 dBA at 1 meter
Battery capacity
two 12 V, 11 ah; extendible
two 12 V, 17 ah; extendible
Recharging time
4 hours typical, 10 hours max.
Communication port
DB9, standard