5. 1000 & 1400 BATTERY INSTALLATION/REPLACEMENT PROCEDURE

Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following proJ
cedure.
1. Grasp the top of the front cover and tilt it out and down.
2. Unhook the bottom of the cover from the chassis and lift it upward to expose the batten door Be careful not to strain the wires. Do

not touch’the exposed printed circuit board.

3. Fold the front cover on top of the UPS as shown.
4. Use a screwdriver or a coin to remove the two battery door screws and open the door.
5. Grasp the tab and gently pull the battery out of the UPS.
6. Disconnect the battery leads Pull the two couples apart to disconnect the battery.
7. Connect the battery leads to the new battery. Note: Small sparks at the battery connectors are normal during battery connection.
8. Slide the battery into the UPS. close the battery door, replace the battery compartment screws, and replace the front cover.
9. Dispose of the old battery properlv at an appropriate recycling facility or return it to the supplier in the packing material for the new

battery. See the new battery instructions for more information.

Battery Bank (Optional)

A special battery bank is available for 1000 & 1400 extended run time version. See your dealer for more information.

6. TROUBLE SHOOTING

23

Problem

UPS will not turn on or off.

All indicators are illuminate and the
UPS emits a constant tone.

UPS beeps and UPS operates onJ
battery even though normal line voltJ
age exists.

UPS does not have expected run
time. Low battery warning or UPS
transfer power to battery but immeJ
diately back to AC.

All indicators are off but the batt. bad
is blinking. no alarm and the UPS is
not operating.

Possible Cause

1. On/off/test button not pushed.
2. Output short or overload shutdown.
3. Computer interface or accessory probJ
lem.

Internal UPS system fault.

1. Sags or spikes is found. UPS is briefly
transferring your equipment to its alterJ
nate power source due to utility voltageJ
sags or spikes.
2. Input circuit breaker is tripped.
3. The UPS has a bad inputJconnection.

1. Low battery condition.
2. Bad battery.

The UPS is shut down and the battery is
discharged from an extended power outJ
age.

Action To Take

1. Press again.
2. Reduce the load then reset the breaker
by pressing the plugger back in.
3. Disconnect the interface then press the
CPU reset button.

1. Press Reset button.
2. Return for service.

1. This operation is normal. The UPS is proJ
tecting your computer equipment from
abnormal utility voltages.
2. Reduce the load and reset the breaker.
3. Cheek the connection.

1. Remove all connected
2. Equipment and recharge
3. Battery for 8 hours.
4. Return for service.

None. The UPS will return to normal operaJ
tion when the power is restored and the
battery has a sufficient charge.