USER’S MANUAL
9. TROUBLESHOOTING
10. SPECIFICATIONS
Situation
Check items
Solution
The UPS is not included. Or it is not
switched off.
1. Main Switch It is not pressed.
2. Short circuit on an output.
3. Overload.
4. A problem with the computer inter
face.
1. Press once again.
2. Disconnect a part of loading.
3. Disconnect the interface and Switch
on once again.
The UPS issues short sound signals and
works in an backup mode even at a
normal input voltage AC power.
1. Input Circuit Breaker is turn off.
2. Bad contact in AC power.
1. Reduce loading and turn on Circuit
Breaker.
2. Check up quality of connection of the
UPS to AC power.
Start UPS but red LED flash.
Low battery power because of long term
AC power failure.
When AC power in normal condition
Execute battery charge for 8 hours.
UPS does not provide the expected
backup time.
The battery may be low power because.
1. Longterm storage.
2. Overload.
3. End of battery life.
1.Charge the battery for 8 hours.
2. Turn off connected applications.
3. Replace the battery.
Red LED Fault illuminates and alarm
continuants beeping.
UPS fault.
Disconnect the output load immediately
and reswitch on the UPS to see if the
«Fault» LED Is still on. If not, your output
load has probably been shorted.
Otherwise, call for service.
Specifications/Model
Smart L 1000
Smart L 2000
Smart L 3000
Maximum load
1000 VA/700 W
2000 VA/1400 W
3000 VA/2100 W
Processor
RISC based micro processor
Detection
Power source RMS value, locked phase, output load, operation temperature,
battery condition & system fault
Protection
Overcurrent, short circuit, latching shutdown, overload, brownout, blackout, input breaker
Communication Port
RS232 standard
Interface connection sup
port
UPSilon 2000 for Novell NetWare, Windows 95/98, Windows NT, Windows ME, Windows 2000,
Windows XP or other Windows Operation Systems, Linux and Free BSD (Basic Version)
Indicators
LED's System fault, Test status, AC normal, Bypass, Load status, Battery capacity
Audible Noise
< 45 dBA at 1m
Intput socket
IEC 320
Screw connection
Output socket
3IEC320+Ger
3IEC320+2Ger
2 Ger+Screw connection
Altitude
0~2000 m up to 40 °C, 30~90% RH Maximum, NonCondensing
Agency Approval
UL. cUL, FCC, [CE,TUV] RusТест
Input (Non Battery Operation)
Voltage Range default
160280 V
Frequency Range
50/60 ±5% (Auto Sensing)
Input Power Factor
> 0.98 (Full Load)
Output (Non Battery Operation)
Voltage Range default
200/220/230/240 V
Wave Form
Sine wave
Over Load Capacity
100 %~120 % delay 60 seconds before switching to bypass; 120 %~150 % delay 10 seconds
before switching to bypass; >150 % immediately switch to bypass