 Owner’s Manual 

SMX1500LCD Digital UPS System

Not suitable for mobile applications.

Español 

Français 



3

6

Important Safety Instructions

SAVE THESE INSTRUCTIONS

The manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these 
warnings will void your warranty.

UPS Location Warnings

•  The UPS is designed for indoor use only in a controlled environment,  

away from excess moisture, temperature extremes, conductive    
contaminants, dust or direct sunlight.

•   Leave adequate space around all sides of the UPS for proper ventilation.

•  Do not mount unit with its front or rear panel facing down (at any  

angle). Mounting in this manner will seriously inhibit the unit's  
internal cooling, eventually causing product damage not covered  
under warranty.

UPS Connection Warnings

•    Connect the UPS directly to a properly grounded AC power outlet. Do not 

plug the UPS into itself; this will damage the UPS.

•    Do not modify the plug of the UPS, and do not use an adapter that 

eliminates the ground connection of the UPS.

•    Do not use extension cords to connect the UPS to an AC outlet. The 

warranty will be void if anything other than Tripp Lite surge suppressors 
are used to connect the UPS to an outlet.

•    If the UPS receives power from a motor-driven AC generator, the 

generator must provide clean, filtered, computer-grade output.

Equipment Connection Warnings

•  Use of this equipment in life support applications where failure of this  

 

equipment can reasonably be expected to cause the failure of the life  

 

support equipment or to significantly affect its safety or effectiveness is not  
recommended. Do not use this equipment in the presence of a flammable    

anesthetic mixture with air, oxygen or nitrous oxide.

•    Do not connect surge suppressors or extension cords to the output of the 

UPS. This might damage the UPS and will void the surge suppressor and 
UPS warranties.

Battery Warnings

•    The UPS does not require routine maintenance. Do not open the UPS for 

 

any reason. There are no user-serviceable parts inside.

•    Batteries can present a risk of electrical shock and burns from high short-

circuit current. Observe proper precautions. Do not dispose of the batteries 
in a fire. Do not open the UPS or batteries. Do not short or bridge the 
battery terminals with any object. Unplug and turn off the UPS before 
performing battery replacement. Use tools with insulated handles. Battery 

replacement should be performed only by authorized service personnel 

using the same number and type of batteries (sealed Lead-Acid). The 
batteries are recyclable. Refer to your local codes for disposal requirements. 
Tripp Lite offers a complete line of replacement batteries at www.tripplite.com.

•   Do not attempt to add external batteries to the UPS.

Quick Installation

STEP  1:  Place  the  UPS  in  a  horizontal  or  vertical  (tower)  position.  To 

install the UPS in a 4-post rack, attach the included hardware to the UPS as 

shown in diagram 

A

. To install the UPS in a 2-post rack, attach the included 

hardware  to  the  UPS  as  shown  in  diagram 

B

. Then,  using  an  assistant  if 

necessary, lift the UPS and attach it to a standard rack with user-supplied 

hardware. Caution: If the UPS is installed in a rack, allow at least 2 cm 
(0.75 in.) clearance above and below the unit. If the UPS is placed flat 
on a surface, do NOT stack any other object directly on top of the unit. 

The  UPS  will  stand  in  a  tower  position  without  the  aid  of  the  included 
hardware. For increased stability, however, Tripp Lite recommends attaching 

the included hardware as shown in diagram 

C

. In either position, the user 

must determine the fitness of hardware and procedures before installation. 

The UPS and included hardware are designed for common rack types and 
may not be appropriate for all applications. The LCD display may be rotated 
to match the orientation of the UPS. Carefully insert a small tool in the slots 
at the side of the LCD to remove it from the UPS housing, then rotate the 
LCD and press it back into place.

CAUTION: To balance the UPS safely when placed in a vertical position, 
make sure the LCD Display is located at the top of the front panel.

STEP 2: Connect a user-supplied power cord* to the UPS, then plug the 

UPS into a wall outlet.**

After plugging the UPS into a wall outlet, push the ON/OFF button for 
one second to turn the UPS on (see 

Basic Operation

 section). 

 

Please Note!

 The UPS 

will not turn on automatically in the presence of 

live utility power. 

*The UPS system does not include an input power cord. The user-supplied power cord should have 
an IEC-320-C13 connector (commonly found on detachable power cords for desktop computers) at 
one end in order to connect to the AC input of the UPS.
**Use an outlet that doesn't share a circuit with a heavy electrical load such as an air conditioner or 
refrigerator.

STEP 3: Plug your equipment into the UPS.

Insert the female connectors of the detachable power cords that came with 
the  UPS  system  into  the AC  inputs  of  the  attached  equipment.  Insert  the 
male connectors into any of the UPS system's available outlets.
The  UPS  is  designed  to  support  electronic  equipment  only.  Connected 
equipment will overload the UPS if the total VA ratings for all the equipment 
connected  to  the  outlets  exceeds  the  UPS  Output  Capacity.  To  find  VA 
ratings, look at equipment nameplates. If the equipment is listed in amps, 
multiply the number of amps by 230 volts to determine VA. (Example: 1 
amp × 230 volts = 230 VA). If unsure whether the outlets are overloaded, 
run a self-test (see “MUTE/TEST” Button description).

STEP  4:  Optional  Installation. 

The  UPS  includes  USB  and  RS-232 

communication  ports  as  well  as  Tel/DSL/Ethernet  and  Coaxial  surge 
protection  jacks.  These  connections  are  optional;  the  UPS  will  work 

properly without these connections.

  Not compatible with PoE (Power over Ethernet) applications.

A

C

B

CAUTION: The UPS must be plugged into a live AC outlet and turned on 
for 24 hours after initial installation to fully charge the internal battery. 
Connected equipment will receive utility-supplied AC power (if present) 
immediately  after  the  UPS  is  plugged  in  and  turned  on,  but  connected 
equipment will not receive full battery backup in the event of a blackout 
or severe brownout unless the internal battery is fully charged.