background image

USER’S MANUAL

7. TROUBLESHOOTING

8. SPECIFICATIONS AND INDICATION TABLE

Problem

Possible Cause

Action To Take

UPS will not turn on or off.

On/off/test button not pressed.
Output short or overload shutdown.

Computer interface or accessory problem.

Press again.
Reduce the load then reset the break"
er by pressing the plunger back in.
Disconnect the interface.

Weak battery /Internal Fault LED
indicators are illuminating and
the UPS emits a constant tone.  

Weak batteries
Internal UPS system fault.

Replace batteries
Return for service.

UPS beeps and UPS operate
on"battery even though normal
line voltage exists.

Sags or spikes are found, UPS is briefly
transferring your equipment to its alter"
nate power source due to utility voltage
sags or spikes.
Input circuit breaker is tripped.
The UPS has a bad input connection.

This operation is normal. The UPS is
protecting your computer equipment
from abnormal utility voltages.

Reduce the load and reset the breaker.
Check the connection.

UPS does not have expected
run time. Low battery warning.

Low battery condition.

Bad battery.

Remove all connected equipment and
recharge battery for 8 hours.
Return for service.

The check battery LED is illumi"
nated and the UPS is not oper"
ating.

The UPS is shut down and the battery is
discharged from an extended power out"
age.

The UPS will return to normal opera"
tion when the power is restored and
the battery has a sufficient charge.

18

Model type

2000

3000

Capacity Rating

2000 VA/1400 W

3000 VA/2100 W

Nominal Input Voltage

220 V

Nominal Input Frequency

50/60 Hz auto sensing

Acceptable Input Voltage

154"261 V

Output Voltage

200"236 V

Output Wave Form

Sine Wave

Continuous Output Capacity

3"5 minute

Typical Back"up Time up to

3"5 minute

Transfer Time

3~6 ms

Processor

RISC based micro processor

Detection

Power source voltage RMS value, locked phase of frequency, output load, bad battery,

battery condition, system fault

Noise filter

Full time EMI/RFI filtering, 100 kHz to 10 MHz

Protection

Over current, Short Circuit, Overload, Surge, Sag, Brownout, Blackout,

Input Breaker, RJ"11/RJ"45

Surge energy rating

1120 Joules

Battery Type

Sealed and leak proof maintenance free lead"acid battery

Battery Capacity

12 V/7 AH (4)

12 V/7 AH (6)

Recharge Time

8 hours typical (Battery Voltage>85%), 10 hours max (Battery Voltage>90%), float charge

Communication Port

RS"232, USB and SNMP card (Optional)

Output Plug Type

6 x IEC 320

Operation Environment

+15 " +25°C, 20"90% Relative Humidity, non condensing

Physical Dimension

633 x 435 x 88 mm

Net Weight

30.15 kg

37.14 kg