USER’S MANUAL

7.7. Test

Under Utility Normal condition, push the “On” Switch for 3 seconds to execute the Battery Self-test function. In case the battery is normal,
it will enter into Battery Backup Mode for 10 seconds then return back to Utility Mode. 
If the battery voltage is detected lower than set limit, the Battery Replacement LED will blink for 5 seconds then extinguish to stop self-test
procedure. And if battery is detected weak or dead, the Battery Replacement LED will steadily illuminate.

7.8. Connect Network Surge protection

Connect a 10 base-T/100 base-T network cable into the RJ-45 network surge protection “IN” jack on the rear of the UPS. Connect from
the “OUT” jack with network cabling to network equipment.

7.9. Replacing the Battery

Note: 

Once the battery is disconnected, the loads are not protected from power outages.

When the Battery Replacement LED(Red) lights up, you may leave the UPS to be re-charged for at least 8~10 hours to see whether the
Red LED will be extinguished after the Self-test Function is executed again. In case the Red LED remains unchanged, you may unscrew
the Easy Swappable Battery cover, replace a new battery than push the “On” Switch to disable the RED LED. 
Please follow the steps 1-7 to replace the new battery

8. UPS AUDIBLE ALARM

16

Øàã 2

Øàã 1

Øàã 3

Øàã 4

Øàã 5

Øàã 6

Øàã 7

IN

O UT

Indicator

Color

Description

Alarm

Utility Mode  

Green

Steady:

Output Load is supplied by Utility

Blinking:

Polarity error or Ground Fault

None

Backup
Mode 

Amber

Steady (with alarm):

Output Load is supplied by Battery

Blinking every 5 seconds (no alarm):

Stand by for Utility

recovery to restart up

Every 2 seconds before bat
tery Low and every 1 second
before battery Cutoff

Fault 

Red

When Overload, short circuit, or
Output Voltage Abnormal occurs

Buzzer beeps continuously

Battery Re
placement 

Red

Blinking:

Battery is weak and needs to be recharged

Steady:

Battery is dead

None