SVEN NEO R 500 инструкция по эксплуатации онлайн - страница 14


Инструкция SVEN NEO R 500 для устройства стабилизатор напряжения содержит страницы на русском языке.

Размер файла: 280.32 kB. Состоит из 16 стр.


Вы можете скачать pdf файл этой инструкции: Скачать PDF


Предыдущая
Следующая
background image

Problem

The AVR does not work.

 

The AVR is on, «

Пере

грузка

» LED does not go 

o

 and there is no output 

voltage.

 The AVR emits repeated 

clicks, though «

Стабили

затор

» LED lights up.

The AVR has disconnected 

the load. «

Перегрузка

» 

LED is on.

Cause

1. The power switch is o

.

2. There is no voltage in the mains 

socket.

3. Too much load is connected. 

1. Failure of the testing scheme.

2. The AVR is faulty.

The input voltage is very unstable.

The input voltage is too high.

Solution

1. Press the power switch again.

2. Make sure there is input 

voltage.

3. Disconnect a part of load.

Switch the AVR o

 and on again. 

If the problem is not solved, 

address  a service center.

It is normal. The AVR is 

regulating the output voltage.

 
When the input voltage reaches 

150–280 V, the AVR will resume 

its operation.

If none of the above methods can solve the problem, please seek professional advice at your 

nearest service center. Never attempt to repair the product yourself. 

5. INSTALLATION AND OPERATION GUIDE

 Connect the load to output sockets of the AVR.

 Connect the AVR to a 220V power line.

 Switch on the power switch. The indicator built into the switch will light up. «

Стабилизатор

» 

(Regulator) LED will light up for a short moment, and «

Перегрузка

» (Overload) and «

Сеть

» (Line) 

LEDs will be on during the whole self-testing.

 After a 10-second self-testing, «

Перегрузка

» (Overload) LED will go o

, «

Сеть

» (Line) LED will 

light up and the voltage will be connected to the output sockets. If «

Перегрузка

» (Overload) LED 

doesn’t go o

 after testing, it’s forbidden to operate the AVR until the trouble is shot.

 When the AVR operates to boost or buck input voltage, the «

Стабилизатор

» (Regulator) LED 

lights up.

 In case of overload or short circuit at the output, the AVR will disconnect voltage supply. After the 

cause of overload is removed, switch on the AVR again by pressing the power switch.

 If the input voltage increases over 280V or falls lower than 150V, the AVR will be disconnected, and 

«

Перегрузка

» (Overload) LED will be on.

6. TROUBLESHOOTING

ENG

13

Automatic Voltage Regulator 